Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Item Number
P226333
Catalog number
BTLM42V710
Description
British Standard fuse-link IEC BS88 gG Type C3 415VAC 240VDC 710A BTLM Central Bolted Tag
EAN/UPC code
3605340268102
Rated voltage AC IEC
415 V
Rated voltage DC IEC
240 V
Rated current
710 A
Speed/Characteristic
gG
Mounting
Bolted
Clearing I2t At Rated Voltage
6720000 A²s
Melting I2t
2400000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
62 W
Contact materials
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
1.36 kg
Product Diameter
82.4 mm
Product Width
0 mm
Product Length
212 mm
Sell Pack Quantity
1 EACH
Sell Pack Weight
1.36 kg
Sell Pack Width
75 mm
Sell Pack Length
235 mm
Sell Pack Height
75 mm