Approvals & Standards
IEC 60282-1
Key features & benefits
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.
Limitor®-PD HV fuses are back-up fuses as defined in the standards: IEC 60282-1 and VDE 0670 T402 and dedicated to protect transformers against effects of short-circuit currents.
The VDE 0670 T402 defines fuses between 6.3A and 160A, for other ratings, thanks to consult Limitor®-P HV fuses range.
To guarantee high quality, Mersen uses the best materials: fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Applications
HV Transformer protection
Documents & Resources
Datasheet
Compliance
项目编号
Z209368
Catalogue No.
45DB360V40PD
Description
变压器用高压 DIN 后备熔断器 Limitor® VDE T402 36kVAC 国际电工委员会 40A d65mm, L537mm 和 撞击器 80N
EAN/UPC 码
3605340218602
额定交流电压 (IEC)
36 kV
Ampere Rating
40 A
熔断器规格
d=65mm, L=537mm
安装
Clip
Clearing I2t At Rated Voltage
14.2 kA²s
AC Max I.R./Breaking Capacity: I1
20 kA
Min Interrupting Rating (MBC)
205 A
Power Dissipation at Rated Current Value
176 W
指示系统
Yes
指示系统类型
Striker
Connection/Terminal Material
Silver-Plated Copper
接线/端子类型
Cylindrical
主体/绝缘材料
Ceramic
产品重量
3.7 kg
产品直径
65 mm
产品长度
603 mm
销售包装数量
1 EACH
销售包装重量
3.7 kg
销售包装宽度
70 mm
销售包装长度
620 mm
销售包装高度
70 mm