Approvals & Standards
Key features & benefits
The production programme of MULTIBLOC® 00.RST9 comprises NH fuse switch disconnectors for 160A.
Products are designed in triple pole units for direct installation on to 40 mm and 60mm bus bar systems.
For installation of MULTIBLOC® NH fuse switch disconnectors of different sizes in distribution units with central cover, respective covers are used to obtain a uniform profile in height and length.
MULTIBLOC® size 00 are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A.
The system is a modular system, which allows the installation and combination of individual components. MULTIBLOC® offers the user the possibility of fast and easy installation as well as a high degree of security during installation and maintenance.
Applications
Documents & Resources
Datasheet
Compliance
项目编号
X1022991
Catalogue No.
3.083.000
Description
NH 熔断器式隔离开关 MULTIBLOC® 尺寸 00 160A 3极 交换 母排系统 60mm 连接 框架夹
EAN/UPC 码
9008567007587
Frequency
50 ... 60 Hz
额定交流电压 (IEC)
690 V
额定直流电压 (IEC)
440 V
Ampere Rating
160 A
使用类别
AC 23 B @ Ue = AC 400 V; Ie = 160 A
使用类别
AC 22 B @ Ue = AC 500 V; Ie = 160 A
使用类别
AC 21 B @ Ue = AC 690 V; Ie = 160 A
使用类别
DC 22 B @ Ue = DC 220 V; Ie = 160 A
使用类别
DC 21 B @ Ue = DC 440 V; Ie = 100 A
开关功能
Triple pole switching
符合 ROHS 标准
Yes
短路电流额定值 (SCCR)
80kA@Ue = AC 400 V; Ie = 160 A / 80kA@Ue = AC 500 V; Ie = 160 A / 80kA@Ue = AC 690 V; Ie = 125 A
熔断器规格
00
极数
3-Pole
污染程度
3
额定负载
uninterrupted duty
Rated Impulse Withstand Voltage
8 kV
额定绝缘电压
1000 V
Rated SC Withstand
4 kA / 1 s
Conventional Free Air thermal Current With Fuse-Links Ith
160 A
约定自由空气发热电流 - 固态熔断体
200 A
熔断体 Pn 的最大功耗
12 W
固态熔断体 Pn 的最大功耗
1.2 W
Power Dissipation by Ith without Fuse-Links
12 W
无固态熔断体时的 Ith 功耗
19 W
采用固态熔断体时的额定短路接通能力 Icm
6.2 kA
安装方式
Bus bar system 60 mm (snap on)
Comments
Cable termination components : 3 frame clamps, Cu 2,5-70 mm², factory assembled
产品重量
0.88 kg
产品宽度
108 mm
产品长度
95.5 mm
产品高度
202 mm
销售包装数量
1 EACH
销售包装重量
0.88 kg
销售包装宽度
111 mm
销售包装长度
205 mm
销售包装高度
120 mm