Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
项目编号
S226313
Catalogue No.
BTC42V100M200
Description
英国标准熔断器 IEC BS88 gM 类型 B1 415VAC 240VDC 100M200A BTC 用螺栓固定
EAN/UPC 码
3605340267907
额定交流电压 (IEC)
415 V
额定直流电压 (IEC)
240 V
In M Ich
100M200 A
速度/特性
gM
安装
Bolted
Clearing I2t At Rated Voltage
293000 A²s
融断 I2t
105000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
8.1 W
Connection/Terminal Material
Tin-Plated Copper
接线/端子类型
Slotted Blades
产品重量
0.24 kg
产品直径
31 mm
产品宽度
0 mm
产品长度
136 mm
销售包装数量
5 EACH
销售包装重量
1.2 kg
销售包装宽度
145 mm
销售包装长度
180 mm
销售包装高度
40 mm