Approvals & Standards
Key features & benefits
The production programme of MULTIBLOC® 1.RST8 comprises NH fuse switch disconnectors for 250A.
Products are designed in triple pole units for direct installation on to 40 mm and 60mm bus bar systems.
For installation of MULTIBLOC® NH fuse switch disconnectors of different sizes in distribution units with central cover, respective covers are used to obtain a uniform profile in height and length.
MULTIBLOC® size 1 are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 1: 250A.
The system is a modular system, which allows the installation and combination of individual components. MULTIBLOC® offers the user the possibility of fast and easy installation as well as a high degree of security during installation and maintenance.
Applications
Documents & Resources
Datasheet
Compliance
项目编号
Q1023054
Catalogue No.
1.001.294
项目描述(ERP)
MB1 250A 3P 1.001.294
Description
MULTIBLOC 1.RST8 size 1 / 250A, 3-pole terminal: clamp strap 1.000.420
EAN/UPC 码
9008567002155
Frequency
50 ... 60 Hz Hz
额定交流电压 (IEC)
690 V
额定直流电压 (IEC)
440 V
Ampere Rating
250 A
使用类别
AC 23 B @ Ue = AC 400 V; Ie = 250 A
使用类别
AC 22 B @ Ue = AC 500 V; Ie = 250 A
使用类别
AC 21 B @ Ue = AC 690 V; Ie = 200 A
使用类别
DC 21 B @ Ue = DC 440 V; Ie = 250 A
开关功能
Triple pole switching
符合 ROHS 标准
Yes
短路电流额定值 (SCCR)
80kA@Ue = AC 400 V; Ie = 250 A / 80kA@Ue = AC 500 V; Ie = 250 A / 50kA (3-,4-pole)@Ue = AC 690 V; Ie = 200 A
熔断器规格
1
极数
3-Pole
污染程度
3
额定负载
uninterrupted duty
Rated Impulse Withstand Voltage
12 kV
额定绝缘电压
1000 V
Rated SC Withstand
8 kA / 1 s
Conventional Free Air thermal Current With Fuse-Links Ith
250 A
约定自由空气发热电流 - 固态熔断体
400 A
熔断体 Pn 的最大功耗
23 W
固态熔断体 Pn 的最大功耗
2.6 W
Power Dissipation by Ith without Fuse-Links
20 W
采用固态熔断体时的额定短路接通能力 Icm
8.2 kA
安装方式
Bus bar system 40 mm and 60 mm
Comments
Cable termination components : 3 clamp straps 70–150 mm²
产品重量
3.06 kg
产品宽度
185 mm
产品长度
110.5 mm
产品高度
246 mm
销售包装数量
1 EACH
销售包装重量
3.06 kg
销售包装宽度
187 mm
销售包装长度
248 mm
销售包装高度
165 mm