Approvals & Standards
IEC 60282-1
Key features & benefits
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.
For the Limitor®-PTS range, Mersen innovates with new fuse-element designs to reduce power losses and new thermal striker to prevent overheating in the fuse compartment of the switch gear.
Mersen uses the best materials : fuse-elements are in pure silver, caps are in copper coated with silver and body is in ceramic.
Limitor®-PTS HV fuse-links are dedicated to protect transformers in combination with air or gas insulated switchgear against the thermal and dynamic effects of short-circuits.
Siemens and Ormazabal recommend Limitor®-PTS HV fuses to be used in their gas-insulated switchgear.
Applications
Best used in SF6 insulated switch gear and compact switch gear
Documents & Resources
Datasheet
Compliance
项目编号
P1018315
Catalogue No.
45DB120V100PTS2
Description
变压器用高压 DIN 后备熔断器 Limitor® VDE T402 12kVAC 国际电工委员会 100A d78mm, L292mm 和 撞击器 热量 80N
EAN/UPC 码
3605340513240
额定交流电压 (IEC)
12 kV
Ampere Rating
100 A
熔断器规格
d=78mm, L=292mm
安装
Clip
Clearing I2t At Rated Voltage
145 kA²s
AC Max I.R./Breaking Capacity: I1
80 kA
Min Interrupting Rating (MBC)
350 A
Power Dissipation at Rated Current Value
105 W
指示系统
Yes
指示系统类型
Striker
Connection/Terminal Material
Silver-Plated Copper
接线/端子类型
Cylindrical
主体/绝缘材料
Ceramic
产品重量
3.2 kg
产品直径
78 mm
产品长度
358 mm
销售包装数量
1 EACH
销售包装重量
3.2 kg
销售包装宽度
75 mm
销售包装长度
390 mm
销售包装高度
75 mm