Approvals & Standards
Key features & benefits
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
The Mersen range of Low Voltage Feeder Pillar Fuse Links are designed for the use with wedge type fuse carriers with fixing centres of 82mm and 92mm. There are primarily for use by Electricity Supply Industries in distribution pillars, open type substation boards, heavy duty service cut-outs and underground disconnecting boxes.
More specificationsApplications
项目编号
H1003911
Catalogue No.
BJU42V160SA
Description
英国标准熔断器 IEC BS88 gG 类型 130x36 415VAC 160A
EAN/UPC 码
3605340479294
额定交流电压 (IEC)
415 V
Ampere Rating
160 A
符合 ROHS 标准
Yes
AC 或 DC
AC
速度/特性
gG
熔断器规格
130x36
安装
夹子
Clearing I2t At Rated Voltage
168000 A²s
融断 I2t
37500 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
10.7 W
Connection/Terminal Material
铜
接线/端子类型
插片
主体/绝缘材料
Ceramic
Comments
BJU
产品重量
0.281 kg
产品直径
36.1 mm
产品长度
130.5 mm
产品高度
41 mm
销售包装数量
3 EA
销售包装重量
0.843 kg
销售包装宽度
180 mm
销售包装长度
140 mm
销售包装高度
65 mm