Approvals & Standards
Key features & benefits
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
The Mersen range of Low Voltage Feeder Pillar Fuse Links are designed for the use with wedge type fuse carriers with fixing centres of 82mm and 92mm. There are primarily for use by Electricity Supply Industries in distribution pillars, open type substation boards, heavy duty service cut-outs and underground disconnecting boxes.
More specificationsApplications
项目编号
D1003930
Catalogue No.
BJU42V400PB
Description
英国标准熔断器 IEC BS88 类型 110x42 415VAC 400A
EAN/UPC 码
3605340478341
额定交流电压 (IEC)
415 V
Ampere Rating
400 A
符合 ROHS 标准
Yes
AC 或 DC
AC
速度/特性
gG
熔断器规格
110x42
安装
夹子
Clearing I2t At Rated Voltage
720000 A²s
融断 I2t
160000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
32 W
Connection/Terminal Material
铜
接线/端子类型
插片
主体/绝缘材料
Ceramic
Comments
BJU
产品重量
0.244 kg
产品直径
41.9 mm
产品长度
110.5 mm
产品高度
31 mm
销售包装数量
3 EA
销售包装重量
0.732 kg
销售包装宽度
145 mm
销售包装长度
140 mm
销售包装高度
53 mm