Approvals & Standards
IEC 60282-1
Key features & benefits
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.
Limitor®-G HV fuses are general purpose fuses as defined in the IEC 60282-1 standard and dedicated to protect transformers against effects of short-circuit currents and low overcurrents.
To guarantee high quality, Mersen uses the best materials: fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Applications
HV Transformer protection
项目编号
A1000155
Catalogue No.
45DG120V40P
Description
变压器用高压 DIN 通用熔断器 Limitor® 12kVAC 国际电工委员会 40A d78mm, L292mm 和 撞击器 80N
EAN/UPC 码
3605340453287
额定交流电压 (IEC)
12 kV
Ampere Rating
40 A
熔断器规格
d=78mm, L=292mm
安装
Clip
Clearing I2t At Rated Voltage
110 kA²s
AC Max I.R./Breaking Capacity: I1
40 kA
Min Interrupting Rating (MBC)
0
Power Dissipation at Rated Current Value
24 W
指示系统
Yes
指示系统类型
Striker
Connection/Terminal Material
Silver-Plated Copper
接线/端子类型
Cylindrical
主体/绝缘材料
Ceramic
产品重量
3.1 kg
产品直径
78 mm
产品长度
358 mm
销售包装数量
1 EACH
销售包装重量
3.1 kg
销售包装宽度
110 mm
销售包装长度
375 mm
销售包装高度