跳转到主要内容

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International Website
Contact us

Approvals & Standards

  • IEC 61643-11
  • EN 61643-11
  • UL 1449 5th Ed.

Key features & benefits

STP T2 40 is the series of Type 2/Class II devices for discharging voltage surges, in accordance with EN/IEC 61643-11. Suitable for the second stage of protection in supply distribution panels in which Type 1 protection devices are installed upstream, or for the first stage of protection in commercial or other applications not exposed to direct strikes and with no external lightning protection system.

More specifications

Applications

  • Building
  • Outdoor LED Lighting
  • Photovoltaic and BESS
  • E-Mobility - EV Charging
  • Industry
  • Telecom
  • Water treatment

Product Specifications

项目编号

83020102  

Catalogue No.

STPT2-30K750V-3P  

Description

Surge Protection Device Type 2, 30kA Imax (8/20), 3Ph, 690/-; 1000/-V, 3+0 TNC, 3 Poles, Pluggable, 3 Modules  

EAN/UPC 码

8435297850946  

符合 ROHS 标准

Yes  

IEC SPD 类型

Class II  

UL SPD 类型

Type 2 Component Assembly  

Format

可插拔  

标称工作电压额定值(Un)

480/830  

AC 或 DC

AC  

最大放电电流:Imax(8/20)

30   kA

Protection Modes

L-PE(N)  

系统配置

TNC  

指示系统

Yes  

指示系统类型

Green (OK) / Not green (replace)  

极数

3-Pole  

Torque Rating

3   N m

Max. Back-Up Fuse

80 A [gG]  

外壳材料

PA66 CT1  

安装方式

DIN 导轨  

Replacement Plug L1

83020007  

产品重量

0.378   kg

产品宽度

54   mm

产品长度

70   mm

产品高度

90   mm

销售包装数量

1   EA

销售包装重量

0.419   kg

销售包装宽度

63   mm

销售包装长度

117   mm

销售包装高度

90   mm